Rated Current Ie
250 A @ 500 VAC
Rated voltage Ue
500 VAC
Rated isolation voltage Ui
1000 VAC
Rated Power Operating Frequency fe
50 Hz
Rated diversity factor RDF
1.0 @ NH-Fuse-Links 400 VAC *
NH-Fuse-Links with clamps
35- 240 rm multi-wire round conductor
35- 300 re single round conductor
50- 240 sm multi-wire sector conductor
50- 300 se single sector conductor
NH-Fuse-Link with screw/bolt for cable lug
M12
Rated Impulse Withstand Voltage Uimp
6 kV
Conditioned Rated Short Cicuit Current
50 kA @ 500 VAC
Rated short-time withstand current with fuse links
50 kA␠ @ 690 VAC
Allowed Ambient Temperature
-25 °C to +40 °C acc. to IEC 61439
Protection by closed housing
IP54
Neutral Disconnector with clamps
Analogue NH-Fuse-Links with clamps
Neutral Disconnector with screw terminal/bolt for cable lug
M12
Earth Connection with screw terminal for cable lug
M12
* Fuse link: max. permissible power dissipation per phase Pn 16.8 W
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: SKD 250A
| Approval Logo | Certificates | Certification Body | Description |
|---|
The product complies with following Guide Lines
| Identification | Details | Initiator | Description |
|---|---|---|---|
|
SCHURTER AG | The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. | |
|
SCHURTER AG | The UKCA marking declares that the product complies with the applicable requirements laid down in the British Amendment of Regulation (EC) 765/2008. | |
|
SCHURTER AG | On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. |
| Designation | Terminal |
Order Number
|
E-No. | Symbols, Footprints, 3D-Models | Free Sample Free Sample
|
Distributor Stock Check Distributor Stock Check
|
... | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SKD 250A E-KL S-KL AE | Terminal/Terminal/External earth | 3-151-293 | 827000008 |
|
... | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| SKD 250A BZ S-KL AE | Bolt/Terminal/External earth | 3-151-294 | 827000018 |
|
... | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| SKD 250A M12 S-KL AE | Screw/Terminal/External earth | 3-151-295 | 827000028 |
|
... | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| SKD 250A 850mm M12 KL AE | Screw/Terminal/External earth | 3-151-296 | ¹⁾ |
|
... | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Factory configuration: Flange inlet 2-piece, single rubber grommet, cable strain relief, centred, Flange outlet stepped grommet, centred 1) Housing large |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Packaging unit | 1 Pcs |